Материал: m013500e_x06

Внимание! Если размещение файла нарушает Ваши авторские права, то обязательно сообщите нам

66 • Feldbus Coupler/Controller

Fieldbus Controller 750-806

3.2.2.4 Display Elements

The operating condition of the fieldbus Coupler or node is signalled via light diodes (LED).

Four LED’s, specific for DeviceNet (OVERFL, RUN, BUSOFF, CONNECT), indicate the module status (MS) or the network status (NS).

 

DeviceNet

 

01

 

02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OVERFL

A

 

 

 

 

 

 

 

C

 

 

 

C

 

 

 

 

MS

 

 

 

 

 

 

 

A

 

 

RUN

B

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

BUS OFF

 

 

 

 

 

 

 

 

 

 

 

24V

 

0V

 

 

 

 

 

 

 

 

 

 

 

NS

 

 

 

 

 

 

 

 

 

 

 

 

CONNECT

 

 

 

 

 

 

 

 

 

 

 

 

I/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

USR

 

 

 

 

 

 

 

 

 

 

 

Fig. 3-23: Display elements 750-806

g080602x

 

 

 

 

 

 

 

 

 

LED

 

 

 

Color

Meaning

 

 

OVERFL

 

 

 

red

Errors or faults at the fieldbus Coupler.

 

 

 

 

 

 

 

 

 

 

RUN

 

 

 

green

Fieldbus Coupler is ready for operation.

 

 

 

 

 

 

 

 

 

BUS OFF

 

 

red

Error or malfunction at network

 

 

 

 

 

 

 

 

CONNECT

 

green

Fieldbus Coupler is ready for network communication.

 

 

 

 

 

 

 

 

 

IO

 

 

 

red

The 'I/O'-LED indicates the operation of the node and signals faults

 

 

 

 

 

/green /

encountered.

 

 

 

 

 

 

orange

 

 

 

 

 

 

 

 

 

 

 

USR

 

 

 

red

The 'USR' LED can be selected by a user program in a programma-

 

 

 

 

 

/green /

ble fieldbus Controller

 

 

 

 

 

 

orange

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

green

Status of the operating voltage system

 

 

 

 

 

 

 

 

 

 

C

 

 

 

green

Status of the operating voltage – power jumper contacts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WAGO-I/O-SYSTEM 750

DeviceNet

Feldbus-Koppler/-Controller • 67

Fieldbus Controller 750-806

3.2.2.5 Configuration and Programming Interface

The configuration and programming interface is located behind the cover flap. This is used to communicate with WAGO-I/O-CHECK and WAGO-I/O-PRO 32 as well as for firmware transfer.

open flap

Configuration and programming interface

Fig. 3-24: Configuration and programming interface

g01xx07e

The communication cable (750-920) is connected to the 4-pole header.

3.2.2.6 Operating Mode Switch

The operating mode switch is located behind the cover flap beside the configuration and programming interface.

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flap

 

 

 

 

 

 

 

Run

Stop

Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(pushing down)

 

 

 

 

 

 

 

 

 

 

 

 

 

Update firmware

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3-25: Operating mode switch

 

 

 

 

 

g01xx10e

The switch is a push/slide switch with 3 settings and a hold-to-run function.

Operating mode switch

Function

From middle to top position

Activate program processing (RUN)

 

 

From top to middle position

Stop program processing (STOP)

 

 

Lower position, bootstrap

For original loading of firmware,

 

not necessary for user

 

 

Push down

Hardware reset

(i.e.with a screwdriver)

All outputs are reset; variables are set to 0 or to FALSE

 

or to an initial value.

 

The hardware reset can be performed with STOP as well

 

as RUN in any position of the operating mode switch!

 

 

An operating mode is internally changed at the end of a PLC cycle.

WAGO-I/O-SYSTEM 750

DeviceNet

68 • Feldbus Coupler/Controller

Fieldbus Controller 750-806

Attention

If outputs are set when switching over the operating mode switch from RUN to STOP, they remain set! Switching off the software side i.e. by initiators, are ineffective, because the program is no longer processed.

Note

With "GET_STOP_VALUE" (library "System.lib") WAGO-I/O-PRO 32 provides a function which serves to recognize the last cycle prior to a program stop giving the user the possibility to program the behavior of the Controller in case of a STOP. With the aid of this function the Controller outputs can be switched to a safe condition.

3.2.2.7 Hardware Address (MAC ID)

The DIP switch is used both for parametrizing (setting the baud rate) of the fieldbus controller and for setting the MAC ID.

The MAC-ID (node address) is set with the DIP switches 1 to 6 by 'sliding' the desired DIP switch to 'ON'.

The binary significance of the individual DIP switches increases according to the switch number. DIP switch 1 being the lowest bit with the value 20 and switch 6 the highest bit with the value 25. Therefore the MAC ID 1 is set with DIP1 = ON, the MAC ID 8 with DIP4 = ON, etc.

For the DeviceNet fieldbus nodes the node address can be set within the range from 0 to 63.

1

1

 

2

2

3

3

4

4

5

5

6

6

7

7

8

8

ON

ON

Fig. 3-26: Example: Setting of station (node) address MAC ID 1 (DIP 1 = ON)

g012540x

The configuration is only read during the power up sequence. Changing the switch position during operation does not change the configuration of the buscoupler. Turn off and on the power supply for the fieldbus controller to accept the DIP switch change.

The default setting is MAC ID 1.

WAGO-I/O-SYSTEM 750

DeviceNet

Feldbus-Koppler/-Controller • 69

Fieldbus Controller 750-806

3.2.2.8 Setting the Baud Rate

The fieldbus controller supports 3 different Baud rates, 125 kBaud, 250 kBaud and 500 kBaud. DIP switches 7 and 8 are used to set the baud rate.

1

1 2

ON

2

 

 

33

44 ON

55

66

7

7

 

8

8

g012541x

Fig. 3-27: Example: Setting the baud rate 250 kBaud (DIP 7 = ON) on a station (node) with the address MAC ID 1.

Baudrate

DIP7

DIP8

125 kBaud*)

OFF

OFF

250 kBaud

ON

OFF

 

 

 

500 kBaud

OFF

ON

 

 

 

not allowed

ON

ON

*) Presetting

 

 

The configuration is only read during the power up sequence. Changing the switch position during operation does not change the configuration of the buscoupler. Turn off and on the power supply for the fieldbus controller to accept the changing.

The default setting is Baud rate 125 kB.

WAGO-I/O-SYSTEM 750

DeviceNet

70 • Feldbus Coupler/Controller

Fieldbus Controller 750-806

3.2.3 Operating System

3.2.3.1 Start-up

The Controller starts-up after switching on the supply voltage or after a hardware reset. The PLC program in the flash memory is transferred to the RAM.

This is followed by the initialization of the system. The Controller determines the I/O modules and the present configuration. The variables are set to 0 or to FALSE or to an initialization value given by the PLC program. The flags retain their status. The "I/O" LED blinks red during this phase.

Following an error free start-up, the Controller changes over to the "RUN" mode. The "I/O" LED lights up green.

A PLC program does not yet exist in the flash memory when delivered. The Controller start-up is described without initializing the system. It then behaves as a Coupler.

3.2.3.2 PLC Cycle

The PLC cycle starts following an error free start-up when the operating mode switch is in the top position or by a start command from the WAGO-I/O-PRO 32. The input and output data of the fieldbus and the I/O modules as well as the times are read. Subsequently, the PLC program in the RAM is processed followed by the output data of the fieldbus and the I/O

modules in the process image. Operating system functions, amongst others, for diagnosis and communication are performed and the times are updated at the end of the PLC cycle. The cycle starts again with the reading in of the input and output data and the times.

The change of the operating mode (STOP/RUN) is made at the end of a PLC cycle.

The cycle time is the time from the start of the PLC program to the next start. If a loop is programmed within a PLC program, the PLC running time and thus the PLC cycle are extended correspondingly.

The inputs, outputs and times are not updated during the processing of the PLC program. This update occurs in a defined manner only at the end of the PLC program. For this reason it is not possible to wait for an event from the process or the elapse of a time within a loop.

WAGO-I/O-SYSTEM 750

DeviceNet