Материал: m013800e

Внимание! Если размещение файла нарушает Ваши авторские права, то обязательно сообщите нам

5.1.2 Data exchange between MODBUS master and I/O modules

The data exchange between the MODBUS master sand coupler is made by bit or byte reading and writing.

In the coupler are 4 different types of process data:

Input words

Output words

Input bits

Output bits

The addresses of the data words in the process illustration of the inputs and outputs are shown in the next illustration:

Fig. 5.2: Data exchange between MODBUS master and I/O modules

MODBUS / Configuration

31

15.12.99

Access word for word to the digital input and output modules is made in accordance with the following table:

Digital inputs/

8.

7.

6.

5.

 

4.

3.

2.

1.

16.

15.

14.

13.

 

12.

11.

10.

9.

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Process data word

Bit

Bit

Bit

Bit

 

Bit

Bit

Bit

Bit

Bit

Bit

Bit

Bit

 

Bit

Bit

Bit

Bit

 

15

14

13

12

 

11

10

9

8

7

6

5

4

 

3

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Byte

 

 

 

High-Byte

 

 

 

 

 

 

Low-Byte

 

 

 

 

 

 

 

 

D1

 

 

 

 

 

 

 

D0

 

 

 

Table 5.10: Allocation of digital inputs/outputs for process data word, coupler

 

 

 

 

 

 

 

 

5.1.3 Addressing the I/O modules

The arrangement of the I/O modules in a node is optional.

The I/O module addressing is based on the attendant coupler.

Addressing is organised word for word and starts with the word address ‘0’ both for the inputs as well as the outputs.

The I/O module addressing corresponds to the sequence of their arrangement behind the coupler. Addressing starts with the bus coupler, which can assign one or more words per channel. This is followed by the I/O module addresses which can assign one or two bits per channel. For the number of input and output bits or bytes please refer to the corresponding I/O module data sheets.

Addressing of I/O modules which are assigned to one or two bits per channel is also made word for word. In other words in each case 16 inputs or outputs are allocated one word. If less channels are present the remaining bits of the word remain free or are reserved for extensions.

If a node is extended by additional I/O modules for which one or more words are assigned per channel, the I/O module addresses are displaced by one or two bits per channel.

Data width ÿ 1 Word / channel

Data width = 1 Bit / channel

Analog input modules

Digital input modules

Analog output modules

Digital output modules

Input modules for thermal elements

Digital output modules with diagnosis (2 Bit / channel)

Input modules for resistance sensors

Power supply modules with fuse holder / diagnosis

Pulse width output modules

Solid State power relay

Interface module

Relay output modules

Up/down counter

 

I/O modules for angle and path measurement

 

Table 5.11: I/O module data width

 

32

MODBUS / Configuration

15.12.99

5.1.4 Application examples

The following figure is an example for a process input image. The configuration comprises of 10 digital and 8 analog inputs. The process image thus has a data length of 8 words for the analog and 1 word for the digital inputs, i.e. 9 words.

Fig. 5.3: Example for process input image, coupler

MODBUS / Configuration

33

15.12.99

The following configuration comprises of 2 digital and 4 analog outputs. This is an example for a process output image. It comprises of 4 words for the analog and one word for the digital outputs.

Fig. 5.4: Example for process output image, coupler

34

MODBUS / Configuration

15.12.99

5.2 Controller

750-812,

750-814,

750-815,

750-816

5.2.1 Settings

As opposed to the MODBUS coupler the factory configuration of the controller change is not made by DIP switch, but is changed using a PC. The communication between the controller and PC is described in the ‘Start-up and diagnosis’ chapter.

The controller is set on the software side using the ‘Fieldbus configuration’ function block of the WAGO-I/O-PRO library. If this module is taken up in the control program, the setting is made automatically even after changing the controller. The settings are taken over into the controller parameter block. If the desired values are not already set, a firmware reset is automatically made in bus operation and the controller restarts with the selected settings.

If the controller is to be set independent of a machine or plant, a program which only comprises of the configuration module can be downloaded and started from the programming system.

Fig. 5.5: Function block for controller setting

The coupler settings are described as follows. Here the term ‘Frame’ is frequently used. ‘Frame’ is a data transfer record.

MODBUS / Configuration

35

15.12.99